Mains Voltage | 230V AC +10% / -15% @ 50/60 Hz |
System Voltage | 24V DC (Nominal) |
Zone Voltage | 21V DC (Nominal) |
Sounder Alarm Output | 2 x 150mA @ 24V DC |
Fault Relay | 1 x Volt Free Relay, SELV @ 1A Max |
Zone Capacity | 32 devices per zone |
Remote sounder operation | Via N/O contact connected to Class Change |
Sounder Activation Delay | 0 to 10 minutes in 1 minute increments |
Zone End of line | 1N4002 Diode (Cathode Stripe to Zone +ve) |
Sounder End of Line | 10K resistor |
Charger Voltage | 27.6V |
Battery cut off | Battery voltage less than 20V |
Battery Internal Resistance limit | 0.9 ohm |
Enclosure size | 371 x 302 x 93 (mm) |
Weight | 3 kg (Excluding Batteries) |
Maximum battery space | 2 x 3.4 Ah, 12 Vdc sealed lead acid |
Thanks for your completed installation of CCTV monitoring system at our flat properly. All systems and online monitoring systems have been explained by your technician to its satisfactory working condition.
Thanks for your completed installation of CCTV monitoring system at our factory. All systems and online monitoring systems have been explained by your technician to its satisfactory working condition.
For more information please contact us....